EGIL™, which incorporates benefits gained from experience with our larger instrument, is intended for circuit breakers with one contact per phase. Smaller and simpler, EGIL is equally versatile – and EGIL's price makes it attractive to small power plants. Moreover, it provides an ideal supplementary instrument for maintenance departments at large power companies.
EGIL is designed to test circuit breakers having one main contact per phase. Its three time channels are connected together on one side. Events at parallel contacts equipped with pre-insertion resistors are recorded and displayed simultaneously. There are two separate time channels for measurement of auxiliary contacts. To simplify on-site hookup, EGIL comes with ready-made multi-cable sets for both main and auxiliary contacts.
Coil currents are measured automatically and presented together with other readings immediately after testing on the display window or via the built-in printer. EGIL is easy to use – a built-in sequencer (program unit) sets the instrument automatically for the next se-quential breaker operation.
Intended primarily for measuring travel (motion), the optional analog input channel finds many other uses as well. If this channel is not installed, all associated menu commands are hidden.
EGIL with the SDRM option together with the SDRM accessory enables static and dynamic resistance measurements.
EGIL can also be equipped with an optional USB interface for com-munication with a PC and the CABA Win™ Circuit Breaker Analysis Software.
SPECIFICATIONS
Specifications are valid at nominal input voltage and an ambient temperature of +25°C, (77°F). Specifications are subject to change without notice.
Environment
Application field The instrument is intended for use in medium-voltage substations and industrial environments.
Temperature
Operating 0°C to +50°C (32°F to +122°F)
Storage & transport -40°C to +70°C (-40°F to +158°F)
Humidity 5% – 95% RH, non-condensing
CE-marking
EMC 2004/108/EC
LVD 2006/95/EC
General
Mains voltage 115 / 230 V AC (switchable), 50 / 60 Hz
Power consumption 100 VA (max)
Dimensions
Instrument 360 x 210 x 190 mm (14.2” x 8.3” x 7.5”)
Transport case 420 x 300 x 230 mm (16.5” x 11.8” x 9.0”)
Weight 6.3 kg (14 lbs). 10 kg (22 lbs) with accessories and transport case
Display LCD
Available languages English, German, French, Spanish, Swedish